A novel PD location technique for MV switchgears based on time of flight method
partial discharge, MV switchgear, time of flight, localization
摘要录用
Jiangjin Cui / Zhuhai Power Supply Bureau, Guangdong Power Grid Corporation, Zhuhai 519000, China
Xiaohong Wu / Zhuhai Power Supply Bureau, Guangdong Power Grid Corporation, Zhuhai 519000, China
Baofeng Nan / Zhuhai Power Supply Bureau, Guangdong Power Grid Corporation, Zhuhai 519000, China
Tingxi Sun / Zhuhai Power Supply Bureau, Guangdong Power Grid Corporation, Zhuhai 519000, China
Insulation faults on medium voltage (MV) switchgears can lead to power outages, disrupting daily domestic activities and economies. An acknowledged solution is to conduct partial discharge (PD) evaluation of MV switchgears. However, the existed PD measurement instruments difficultly identify the exact PD-affected switchgear in a row of switchgears, causing their PD evaluation laborious and time-consuming. Therefore, this paper develops a novel PD location technique for MV switchgears. The technique is based on the time of flight (TOF) method, which detects the orientation of PD source by identifying the difference of time of arrival (DTOA) between the PD signals arriving at the two enabled sensors. A time-sharing mechanism is proposed to ensure the TOF method to be available for multiple sensors and simultaneously minimize the number of expensive high-speed acquisition chips. Wiener filter is used to calculate the DTOA from time domain waveforms of the detected PD pulses. The efficiency of the proposed technique was validated in three 10 kV metal-clad switchgears in laboratory.

 
重要日期
  • 会议日期

    09月25日

    2022

    09月29日

    2022

  • 08月15日 2022

    提前注册日期

  • 09月10日 2022

    报告提交截止日期

  • 11月10日 2022

    注册截止日期

  • 11月30日 2022

    初稿截稿日期

  • 11月30日 2022

    终稿截稿日期

主办单位
IEEE DEIS
承办单位
Chongqing University
移动端
在手机上打开
小程序
打开微信小程序
客服
扫码或点此咨询