129 / 2022-03-13 23:52:36
Cracks Detection under Porcelain Insulator Flange by Pulsed Thermography
Porcelain Insulator,Cracks Detection,Pulsed Thermography,Lucy-Richardson Iteration,diameter depth ratio
终稿
Zekai Shen / Tsinghua Shenzhen International Graduate School
Hongwei Mei / Tsinghua Shenzhen International Graduate School
Yanxin Tu / Tsinghua Shenzhen International Graduate School
Rui Sun / Tsinghua Shenzhen International Graduate School
Chenjun Guo / Ltd.;Electric Power Research Institute of Yunnan Power Grid Co.
Liming Wang / Tsinghua Shenzhen International Graduate School
The crack under flange is the key factor inducing insulator fracture. This work introduces the pulsed thermography (PT) to detect the surface cracks of porcelain insulator hidden under the flange. A pulsed thermography system with darkroom and fast infrared camera was designed and built. The effectiveness of the method was demonstrated by the experiment of artificial samples. The thermal response was determined as the radiation difference between the defect area and defect-free area. Feature images were obtained according to the time point of the maximum thermal response. It is verified that the maximum metal layer depth applied by this method is 4-6mm under the temperature resolution of 18mK. The time domain feature images obtained by detection were optimized by Lucy-Richardson literation to improve the visual effect, so that the narrow defects and defect boundaries could be more accurately distinguished.
重要日期
  • 会议日期

    09月25日

    2022

    09月29日

    2022

  • 08月15日 2022

    提前注册日期

  • 09月10日 2022

    报告提交截止日期

  • 11月10日 2022

    注册截止日期

  • 11月30日 2022

    初稿截稿日期

  • 11月30日 2022

    终稿截稿日期

主办单位
IEEE DEIS
承办单位
Chongqing University
移动端
在手机上打开
小程序
打开微信小程序
客服
扫码或点此咨询