Analysis of influencing factors of 750 kV controlled closing circuit breaker based on field actual operation data
controlled closing,circuit breaker,ACF
摘要录用
Hui Ni / Electric Power Research Institute of State Grid Ningxia Electric Power Company Limited
Feiyue Ma / Electric Power Research Institute of State Grid Ningxia Electric Power Company Limited
Zhonghua Xiang / State Grid Ningxia Electric Power Company Limited
Wei Li / State Grid Ningxia Electric Power Company Limited
Phase controlled closing circuit breaker has been applied in closing capacitor, filter and converter. Although it is widely used, the effect of ambient temperature on its phase selection performance has not been deeply studied. In the past, this work was only carried out in the laboratory, and it was not under actual high voltage. This paper takes the filter field circuit breaker of the controlled closing converter station as the research object. Due to the frequent switching of the filter, a large number of switching data can be obtained, and through the field device, the closing time, ambient temperature, idle time, control voltage and other data can be obtained for research.  According to the research of this paper, for the controlled closing circuit breaker, it is most important to consider the influence of ambient temperature. In addition, it is clear that the mechanical dispersion is moderate within ± 1ms before putting into operation. RDDS performance cannot be fully verified in laboratory and field.



 
重要日期
  • 会议日期

    09月25日

    2022

    09月29日

    2022

  • 08月15日 2022

    提前注册日期

  • 09月10日 2022

    报告提交截止日期

  • 11月10日 2022

    注册截止日期

  • 11月30日 2022

    初稿截稿日期

  • 11月30日 2022

    终稿截稿日期

主办单位
IEEE DEIS
承办单位
Chongqing University
移动端
在手机上打开
小程序
打开微信小程序
客服
扫码或点此咨询