Determination of proper Blocking tap changer Threshold voltage to Prevent Long-term Voltage Collapse: Practicable Scenario in KEPCO System
编号:66 访问权限:仅限参会人 更新:2020-11-11 12:09:28 浏览:149次 口头报告

报告开始:暂无开始时间(12)

报告时间:暂无持续时间

所在会场:[暂无会议] [暂无会议段]

暂无文件

摘要
This paper determined proper blocking tap changer threshold voltage as countermeasure to prevent cascading failure in KEPCO system. Cascading failures are difficult to address with centralized emergency control because of unexpected characteristics depending on power system conditions. This results is an approach for fast and conservative installation in a system that has no countermeasures. The performance of the proposed method is described by applying to the practicable cascading failure scenario in Korean power systems (KEPCO system) with explanation of simulation environments to derive long-term voltage instability. The proposed strategy effectively copes with cascading failures contingencies by preventing the voltage collapse to ensure reliability and reducing the unnecessary operation of on load tap changer to improve the reasonability.
关键词
Cascading Failure,Long-term voltage stability,Blocking tap changer