Optimal Arrester Configuration Scheme for Series Compensation Devices
编号:298 访问权限:仅限参会人 更新:2020-11-11 12:10:24 浏览:187次 张贴报告

报告开始:暂无开始时间(12)

报告时间:暂无持续时间

所在会场:[暂无会议] [暂无会议段]

暂无文件

摘要
When the grounding fault occurs at the network side of the series compensation device, there will be a large temporary overvoltage between the terminals. Based on the analysis of overvoltage, the thyristor bypass switch (TBS) with microsecond hardware is used to transfer the fault current through the device rapidly, which makes the arrester produce instantaneous impulse residual voltage only at the natural commutation point, effectively reduces the voltage ratio of the arrester, and then the optimal configuration scheme of the arrester with series compensation device is put forward. Taking the large capacity hybrid unified power flow controller as an example, the basic parameters of arrester are determined by RTDS transient simulation calculation, and the voltage of each measuring point before and after arrester configuration is compared and analyzed through simulation model checking, so as to determine the rationality of arrester configuration.
关键词
Arrester configuration,large-capacity hybrid unified power flow controller,Series Compensation,thyristor bypass switch
报告人
Zhang Yifan
North China Electric Power University

稿件作者
Ge Jing Global Energy Interconnection Researching Institute Co. ,Ltd.
Liu Haijun Global Energy Interconnection Researching Institute Co. ,Ltd.
Zhang Yifan North China Electric Power University
Song Jieying Global Energy Interconnection Researching Institute Co. ,Ltd.
Zhao Guoliang Global Energy Interconnection Researching Institute Co. ,Ltd.
发表评论