Control Scheme of Y-connected Modular Multilevel Converter in Fractional Frequency Transmission System Under Unbalanced Grid Fault
编号:242
访问权限:仅限参会人
更新:2020-11-11 12:10:13 浏览:155次
张贴报告
摘要
Y-connected modular multilevel converter (Y-MMC) is a new topology of direct AC/AC power conversion, with competitive application prospects in Fractional Frequency Transmission System (FFTS). To improve the uninterrupted operation capability of Y-MMC, the control strategy considering unbalanced grid fault is proposed in this paper. This paper proposes the mathematical model of Y-MMC under asymmetric grid conditions according to the symmetrical component method and superposition principle of linear systems. Based on the proposed mathematical model, positive and negative sequence current inner loop controller, and outer loop controller to suppress the negative sequence current are specially designed for the stable operation of Y-MMC under asymmetric grid conditions. The effectiveness of the proposed control strategy has been verified by the simulation results obtained from a 10 kV, 10 MW Y-MMC system built in MATLAB /Simulink.
关键词
negative sequence current,symmetrical component method,Y-connected modular multilevel converter,fractional frequency transmission system,unbalanced grid fault
稿件作者
Jianyang Yu
Xi’an Jiaotong University
Ting Yu
Northwest University of Political Science and Law
Yongqing Meng
Xi’an Jiaotong University
发表评论