The reactive power control of variable power controlled LCC HVDC in GW level wind power integration
编号:146
访问权限:仅限参会人
更新:2020-11-11 12:09:48 浏览:150次
张贴报告
摘要
The LCC HVDC may be an effective way to transmit large wind power to load center. Because of variability of wind power, the variable power controlled LCC HVDC should be used. However, the reactive power will fluctuate frequently, and the filter and tap will also be switched frequently. A new control method including constant Udi0 control and rectifier AC voltage control is put forward to adjust the firing angle of invertor and keep the reactive power not changed so much, which can reduce the number of shunt filters/capacitors switching number and transformer tap stepping number. The reactive power control method is very important and practical for large wind power integration into power system.
关键词
LCC HVDC, filter switching, reactive power control, variable power control, wind power
稿件作者
Cai Rong
ABB
Yue ChengYan
ABB
Hou JunXian
ABB
Li Yan
CEPRI
Liu Chao
CEPRI
发表评论