859 / 2019-04-30 01:22:58
An Accident Analysis of Circuit Breaker in HVDC Converter Station Filter Branch
arc fault,AC filter,dynamic arc model,overvoltage,circuit breaker
全文录用
Chunying HE / Xi'an Jiaotong University
Xiaoguang Zhu / Xi'an Jiaotong University
Junbo Deng / Xi'an Jiaotong University
Xiaohui Chen / Xi'an Jiaotong University
Yubo Guo / Xi'an Jiaotong University
In the HVDC transmission systems, AC filter circuit breakers (CB) are switched frequently to keep the balance of reactive power. CB stays under AC/DC hybrid conditions since the current flowing through AC filter is capacitive. Moreover, due to the differences between the resistances of multiple breaks, the unbalanced voltage distribution is easy to occur, which will cause a high transient overvoltage on one break among them. In recent years, the circuit breaker explosion accidents have occurred many times. In this paper, a real case of the AC filter arc fault is briefly described. Based on PSCAD, a simulation model is established for CB and dynamic arcing resistance. The combination of simulation results and strip inspections of on-site CB confirms the reasons for the arc fault and provides a basis for the operation and maintenance of AC filter in HVDC converter stations.
重要日期
  • 会议日期

    10月21日

    2019

    10月24日

    2019

  • 10月13日 2019

    摘要录用通知日期

  • 10月13日 2019

    初稿截稿日期

  • 10月14日 2019

    初稿录用通知日期

  • 10月24日 2019

    注册截止日期

  • 10月29日 2019

    终稿截稿日期

承办单位
Xi'an Jiaotong University
联系方式
移动端
在手机上打开
小程序
打开微信小程序
客服
扫码或点此咨询