638 / 2019-04-12 19:29:12
An FCL Optimal Configuration Method for Reducing the Risk of Successive Commutation Failure in MI-HVDC Systems
Successive commutation failure,fault current limiter,multi-infeed interaction factor,HVDC
摘要录用
Successive commutation failure is one of the common faults in multi-infeed HVDC system (MI-HVDC), which has a huge adverse impact on the operation of power systems. Fault current limiter (FCL) is a device that can be used for limiting the risk of successive commutation failure by reducing the voltage interactions among different HVDCs. This paper proposes an optimization model for optimal location and parameter selection of FCL to suppress the successive commutation failure. The decrease in the Multi-infeed interaction factor (MIIF) after the FCLs are installed is considered as the goal. Meanwhile, the installation cost of FCLs is bounded. A greedy algorithm is used to solve the optimization problem. Finally, a modified IEEE 118-bus system is used to validate the effectiveness of the proposed model.
重要日期
  • 会议日期

    10月21日

    2019

    10月24日

    2019

  • 10月13日 2019

    摘要录用通知日期

  • 10月13日 2019

    初稿截稿日期

  • 10月14日 2019

    初稿录用通知日期

  • 10月24日 2019

    注册截止日期

  • 10月29日 2019

    终稿截稿日期

承办单位
Xi'an Jiaotong University