53 / 2018-08-20 16:22:33
Effect of Frequency on Discharge Characteristics of Inter-layer Materials in HV-HF transformers
voltage frequency,thermal breakdown,surface discharge,insulation lifetime,inter-layer materials
终稿
Zhao Yikun / Insititute of Electrical Engineering of the Chinese Academy of Sciences
Zhang Guoqiang / Institute of Electrical Engineering Chinese Academy of Sciences
Guo Runrui / Institute of Electrical Engineering of the Chinese Academy of Sciences
Li Kang / Institute of Electrical Engineering of the Chinese Academy of Sciences
Han Yu / Global Energy Interconnection Research Institute
Gong Xuehai / Global Energy Interconnection Research Institute
High-voltage high-frequency (HV-HF) transformers are usually operated at a non-sinusoidal voltage with a frequency of 1~20 kHz, and its working frequency has a significant impact on discharge behaviors of inter-layer insulation materials. In order to investigate the influence of voltage frequency on discharge characteristics, an experimental platform with a high frequency power source is set up. Two kinds of inter-layer insulation materials, all of which have excellent thermostability, including the NHN insulation paper which can be resisted high temperature for class H and the modified DMD paper which can be resisted high temperature for class F, are used as test samples. Discharge characteristics tests, including breakdown and surface discharge, are conducted on thermostable inter-layer insulation materials by adjusting applied voltage from 0 kV to 20 kV, and frequency from 1 kHz to 20 kHz, under bipolar high frequency square wave excitation power supply. In terms of high frequency breakdown characteristics, the two-parameter Weibull statistic method is used to calculate the probability of insulation failure, and the relationship between breakdown voltage and frequency is analyzed. The surface discharge characteristics under high frequency is another important research content. The flashover voltage-frequency (V-f) discharge characteristic is analyzed based on the Secondary Electron Emission Avalanche (SEEA) model. The experiment results show that, the scale parameter α which is also called the characteristic value of breakdown voltage based on the Weibull distribution decreases with the increase of voltage frequency. Thermal effect is the main reason for the drop of breakdown voltages. In addition, frequency has almost no effect on the surface discharge inception while the flashover voltage is significantly reduced with the increasing frequency. Through the surface insulation tests on DMD paper, it is found that the high-frequency effect has greatly reduced the insulation lifetime.
重要日期
  • 会议日期

    04月07日

    2019

    04月10日

    2019

  • 04月10日 2019

    注册截止日期

  • 05月12日 2019

    初稿截稿日期

主办单位
IEEE电介质和电气绝缘协会
中国电工学会工程电介质专业委员会
承办单位
华南理工大学
移动端
在手机上打开
小程序
打开微信小程序
客服
扫码或点此咨询