Research on the effect of different connection test methods on frequency response of transformer windings
Transformer winding,Frequency response,Test method,Winding deformation
终稿
Cao Yang / Electric Power Research Institute.CSG
Wang Zhiming / Electric Power Research Institute.CSG
Xu Aidong / Electric Power Research Institute.CSG
Li Licheng / China Southern Power Grid
Li Peng / Electric Power Research Institute.CSG
Ming Zhe / Electric Power Research Institute.CSG
Wu Zhibing / Electric Power Research Institute.CSG
Different test methods of connecting wire have great influence on frequency response of transformer windings. In order to research the influence of different test methods, the experimental system is established, and the characteristics of winding frequency response under proposed test methods in existing standards are compared and analyzed through experiments. The following conclusions are drawn for the test transformer: During the test process, whether the untested winding ports are shorted will result in obvious deviation on the frequency response of the test winding, and different test methods affect different frequency bands. The frequency response curves of the test winding in the frequency range below 100 kHz and in the frequency range around 1 MHz are obviously affected by whether the untested winding ports are shorted. Injection port has obvious influence on inter-winding frequency response measurement. For this transformer, the major change will appear above 100 kHz. This method has certain superiority for fault diagnosis, such as the diagnosis for radial deformation and the judgment of faulty windings.
重要日期
  • 会议日期

    04月07日

    2019

    04月10日

    2019

  • 04月10日 2019

    注册截止日期

  • 05月12日 2019

    初稿截稿日期

主办单位
IEEE电介质和电气绝缘协会
中国电工学会工程电介质专业委员会
承办单位
华南理工大学
移动端
在手机上打开
小程序
打开微信小程序
客服
扫码或点此咨询